Electrode level relay ST/NR

The relay is mainly used in applications in which containers are automatically filled and drained. In addition, it is also utilised as protection against containers overfilling or running dry.

The electrode level relay ST/NR can be operated with single-pole electrodes when using an earth electrode or with two-pole electrodes.
If the level of the liquid reaches the upper electrode a start command is issued to the pump. As soon as the liquid level drops below the electrode a stop command is issued to the pump.
Alternating voltage is utilised to prevent electrolytic degradation.
That limits the length of cable between the electrode and the device.
The response sensitivity can be set via the integrated potentiometer.
LEDs indicate the actual control state of the relay.

Principal functions:

  • Adjustable response sensitivity
  • Pluggable housing

Technical data

Operation voltage 230 V / 50 Hz
Power consumption ca. 2VA
Electrode voltage 24 V / 50 Hz
Distance to measuring point ca. 50 m
Output contacts 1 Wechsler, potentialfrei
Switching capacity 250 V / 50 Hz, 2 A, max. 200 VA
Response sensitivity 0-100 / 200 kΩ
Housing Kunststoff, ABS
Degree of protection IP 20
Emission
Immunity

Handling is very simple and reliable.